                             CERT-Renater

                 Note d'Information No. 2020/VULN707
_____________________________________________________________________

DATE                : 24/12/2020

HARDWARE PLATFORM(S): /

OPERATING SYSTEM(S): Systems running Treck TCP/IP versions prior
                                      to 6.0.1.68.

=====================================================================
https://us-cert.cisa.gov/ics/advisories/icsa-20-353-01
_____________________________________________________________________

ICS Advisory (ICSA-20-353-01)


Treck TCP/IP Stack

Original release date: December 18, 2020


Legal Notice

All information products included in https://us-cert.cisa.gov/ics are
provided "as is" for informational purposes only. The Department of
Homeland Security (DHS) does not provide any warranties of any kind
regarding any information contained within. DHS does not endorse any
commercial product or service, referenced in this product or otherwise.
Further dissemination of this product is governed by the Traffic Light
Protocol (TLP) marking in the header. For more information about TLP,
see https://us-cert.cisa.gov/tlp/.


1. EXECUTIVE SUMMARY

    CVSS v3 9.8
    ATTENTION: Exploitable remotely
    Vendor: Treck Inc.
    Equipment: TCP/IP
    Vulnerability: Heap-based Buffer Overflow, Out-of-bounds Read,
                   Out-of-bounds Write

The Treck TCP/IP stack may be known by other names such as Kasago
TCP/IP, ELMIC, Net+ OS, Quadnet, GHNET v2, Kwiknet, or AMX.


2. RISK EVALUATION

Successful exploitation of this vulnerability may allow remote code
execution and a denial-of-service condition.


3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS

The following components of Treck TCP/IP stack Version 6.0.1.67 and
prior are affected:

    HTTP Server
    IPv6
    DHCPv6

3.2 VULNERABILITY OVERVIEW

3.2.1    HEAP-BASED BUFFER OVERFLOW CWE-122

A vulnerability in Treck HTTP Server components allow an attacker to
cause a denial-of-service condition. This vulnerability may also result
in arbitrary code execution.

CVE-2020-25066 has been assigned to this vulnerability. A CVSS v3 base
score of 9.8 has been calculated; the CVSS vector string is
(AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).


3.2.2    OUT-OF-BOUNDS WRITE CWE-787

An out-of-bounds write in the IPv6 component may allow an
unauthenticated user to potentially cause a possible denial-of-service
via network access.

CVE-2020-27337 has been assigned to this vulnerability. A CVSS v3 base
score of 9.1 has been calculated; the CVSS vector string is
(AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H).


3.2.3    OUT-OF-BOUNDS READ CWE-125

An issue was discovered in Treck IPv6. An out-of-bound read in the
DHCPv6 client component may allow an unauthenticated user to cause a
possible denial-of-service via adjacent network access.

CVE-2020-27338 has been assigned to this vulnerability. A CVSS v3 base
score of 5.9 has been calculated; the CVSS vector string is
(AV:A/AC:H/PR:N/UI:N/S:U/C:H/I:N/A:H).


3.2.4    OUT-OF-BOUNDS READ CWE-125

Improper input validation in the IPv6 component may allow an
unauthenticated user to cause an out-of-bounds read of up to three bytes
via network access.

CVE-2020-27336 has been assigned to this vulnerability. A CVSS v3 base
score of 3.7 has been calculated; the CVSS vector string is
(AV:N/AC:H/PR:N/UI:N/S:U/C:L/I:N/A:N).


3.3 BACKGROUND

    CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing, Information
Technology, Healthcare and Public Health, Transportation Systems

    COUNTRIES/AREAS DEPLOYED: Worldwide
    COMPANY HEADQUARTERS LOCATION: United States


3.4 RESEARCHER

Intel reported these vulnerabilities to Treck.


4. MITIGATIONS

Treck recommends users apply the latest version of the affected products
(Treck TCP/IP 6.0.1.68 or later versions). To obtain patches, email
security@treck.com

Treck recommends users who cannot apply the latest patches to implement
firewall rules to filter out packets that contain a negative content
length in the HTTP header.

For more detailed information on the vulnerabilities and the mitigating
controls, please see the Treck advisory.

CISA recommends users take defensive measures to minimize the risk of
exploitation of this vulnerability. Specifically, users should:

    Minimize network exposure for all control system devices and/or
systems, and ensure that they are not accessible from the Internet.

    Locate control system networks and remote devices behind firewalls,
and isolate them from the business network.

    When remote access is required, use secure methods, such as Virtual
Private Networks (VPNs), recognizing that VPNs may have vulnerabilities
and should be updated to the most current version available. Also
recognize that VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended
practices on the ICS webpage on us-cert.cisa.gov. Several recommended
practices are available for reading and download, including Improving
Industrial Control Systems Cybersecurity with Defense-in-Depth
Strategies.

Additional mitigation guidance and recommended practices are publicly
available on the ICS webpage on us-cert.cisa.gov in the Technical
Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion
Detection and Mitigation Strategies.

Organizations observing any suspected malicious activity should follow
their established internal procedures and report their findings to CISA
for tracking and correlation against other incidents.

High skill level is needed to exploit. No known public exploits
specifically target these vulnerabilities.


Contact Information

For any questions related to this report, please contact the CISA at:

Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870

For industrial control systems cybersecurity information:
https://us-cert.cisa.gov/ics
or incident reporting:  https://us-cert.cisa.gov/report

CISA continuously strives to improve its products and services. You can
help by choosing one of the links below to provide feedback about this
product.


=========================================================
+ CERT-RENATER       |    tel : 01-53-94-20-44          +
+ 23/25 Rue Daviel   |    fax : 01-53-94-20-41          +
+ 75013 Paris        |    email:cert@support.renater.fr +
=========================================================